EV Charger Wire & Breaker Size Calculator
Charger amps in, breaker and copper or aluminum conductor out, for THHN in conduit or NM-B cable.
60 A breaker, 6 AWG Cu
How the size is worked out
NEC 625.41 treats EV charging as a continuous load: the branch circuit and its breaker must be rated at least 125% of the charger's maximum current. A 48 A charger needs 48 × 1.25 = 60 A, so a 60 A two-pole breaker.
The conductor then has to carry at least that 125% figure in the right column of Table 310.16. With breakers and chargers whose terminals are rated 75 °C, THHN or THWN-2 in conduit can use the 75 °C column. NM-B cable is limited to the 60 °C column (334.80), so it often needs one size larger. The ground comes from Table 250.122, based on the breaker.
Common sizes at a glance
| Charger | Breaker | Cu THHN 75 °C | Cu NM-B 60 °C |
|---|---|---|---|
| 16 A | 20 A | 12 AWG | 12 AWG |
| 24 A | 30 A | 10 AWG | 10 AWG |
| 32 A | 40 A | 8 AWG | 8 AWG |
| 40 A | 50 A | 8 AWG | 6 AWG |
| 48 A | 60 A | 6 AWG | 4 AWG |
| 64 A | 80 A | 4 AWG | 3 AWG |
| 80 A | 100 A | 3 AWG | 1 AWG |
Before you pull wire
- Check the charger's installation manual: it lists the breaker it expects.
- Long run? Check the drop with the voltage drop calculator. If you upsize for drop, 250.122(B) says the ground is upsized in proportion.
- Adjust for more than three current-carrying conductors in a raceway, or high ambient temperatures, before using the table value.
- Make sure the panel can carry it first, with the load calculator.
Run the numbers on site
Panel load, wire size, voltage drop and a PDF quote in one app.

FAQ
Questions people ask
Short answers about this free tool.
What size wire for a 48 amp EV charger?
A 60 A circuit: 6 AWG copper THHN/THWN-2 in conduit with 75 °C terminations, or 4 AWG copper NM-B cable. Aluminum in conduit needs 4 AWG.
What size breaker for a 40 amp charger?
50 A. A 40 A charger is a continuous load, so 40 × 1.25 = 50 A. That's why a 40 A charger is the largest that can plug into a 50 A NEMA 14-50 receptacle.
Can I use the 90 °C column for THHN?
Only for adjustment and correction factors. The final ampacity can't exceed the terminal rating, which is 75 °C at best for typical breakers and chargers (110.14(C)).
Is aluminum wire OK for an EV charger?
Yes, with terminals rated for aluminum (AL/CU) and proper torque. It is one or two sizes larger than copper for the same circuit.