EV Charger Load Calculator
NEC 220.82 optional method for dwellings: will the charger fit on this service?
125.5 A of 200 A
How the load calculator works
It follows NEC 220.82, the optional method for a dwelling unit served by a 120/240 V, 3-wire service of 100 A or more. The general load is 3 VA per square foot, 1,500 VA for each small-appliance and laundry circuit, and the nameplate rating of fixed appliances, including the EV charger at its full rating. The first 10 kVA counts at 100% and the rest at 40%.
Then it adds the largest of the heating and cooling loads: air conditioning at 100%, central electric heat or fewer than four separately controlled heaters at 65%, four or more separately controlled heaters at 40%, or a heat pump compressor at 100% plus 65% of its supplemental heat. The total divided by 240 V is the calculated load in amps.
When the charger doesn't fit
- Turn the charger down. A 32 A setting on a 40 A circuit adds 7,680 VA instead of 11,520 VA, and still adds about 25–30 miles of range an hour for most cars. Under 625.42 the adjusted setting counts if it is behind restricted access.
- Use load management. An energy management system (625.42, 750.30) lets the charger use spare capacity and throttle back when the house load is high.
- Measure instead of calculating. For an existing home, 220.87 lets you use the highest demand over the last 12 months, times 125%, plus the new load. It often shows more room than 220.82.
- Upgrade the service when none of these is enough. See our worked 220.82 example.
What it does not cover
Local amendments, utility rules and the 220.87 existing-load method are outside this calculator, and 220.82 applies to dwellings only. Size the branch circuit with the wire and breaker calculator. Results are estimates for professionals; the installer and the AHJ have the final word.
Run the numbers on site
Panel load, wire size, voltage drop and a PDF quote in one app.

FAQ
Questions people ask
Short answers about this free tool.
Is the calculator free?
Yes. It runs in your browser with no account, and the app's calculators are free too.
Which code edition is it based on?
NEC 2023. The 220.82 method is essentially unchanged from 2017 and 2020, but check which edition your jurisdiction has adopted.
What if the result is over 100%?
Options are a lower charger setting, a load-managed charger (energy management system per 625.42 and 750.30), a 220.87 calculation from real demand data, or a service upgrade.
Can I use it for commercial jobs?
No. 220.82 applies to dwelling units. Commercial services use the standard method in Article 220, Part III.