What Size Wire for a 48 Amp EV Charger?
60 A breaker, 6 AWG copper THHN in conduit or 4 AWG NM-B: why the cable type changes the answer, plus aluminum, the ground, conduit size and long runs.
The EV Charger Calc team
Nov 22, 2026 · 3 min read

A 48 A charger is the most common hardwired Level 2 install, and the wire size question has two right answers depending on how you run it. Here's why, and which one to use.
Step 1: 48 A becomes 60 A
NEC 625.41 treats EV charging as a continuous load. The branch circuit and the overcurrent device must be at least 125% of the charger's maximum load:
48 A × 1.25 = 60 A
So: a 60 A two-pole breaker, and conductors with an ampacity of at least 60 A.
Step 2: pick the column
Table 310.16 gives three ampacities for each size: the 60 °C, 75 °C and 90 °C columns. Which one you can use depends on the wiring method and the terminals.
- 110.14(C): the final ampacity can't exceed the temperature rating of the weakest termination. Breakers and chargers are usually rated 75 °C.
- 334.80: NM-B cable is limited to the 60 °C column, whatever its conductors are rated.
- THHN/THWN-2 in conduit is rated 90 °C, but with 75 °C terminals you use the 75 °C column. The 90 °C value is only a starting point for derating.
THHN in conduit: 6 AWG copper
With 75 °C terminations on both ends, 6 AWG copper THHN is good for 65 A in Table 310.16, which covers the 60 A circuit.
Aluminum in conduit needs 4 AWG (65 A at 75 °C), with terminals marked AL/CU.
NM-B cable: 4 AWG copper
NM-B is limited to the 60 °C column. 6 AWG NM-B is only 55 A, not enough for a 60 A continuous load, so step up to 4 AWG NM-B (70 A).
Since 4 AWG NM-B is expensive and stiff, many electricians run 6 AWG THHN in conduit instead, especially in a garage where the run is exposed anyway.
The whole circuit at a glance
| Part | Copper in conduit | NM-B cable | Aluminum in conduit |
|---|---|---|---|
| Breaker | 60 A 2-pole | 60 A 2-pole | 60 A 2-pole |
| Conductors | 6 AWG THHN/THWN-2 | 4 AWG copper NM-B | 4 AWG XHHW-2 or THHN |
| Ampacity used | 65 A (75 °C) | 70 A (60 °C) | 65 A (75 °C) |
| Ground (250.122) | 10 AWG Cu | In the cable | 8 AWG Al or 10 AWG Cu |
Two 6 AWG THHN conductors and a 10 AWG ground fit comfortably in 3/4 in EMT; check Chapter 9 fill if you add a neutral or other circuits.
Other charger sizes
| Charger | Circuit | Cu THHN (75 °C) | Cu NM-B (60 °C) |
|---|---|---|---|
| 32 A | 40 A | 8 AWG | 8 AWG |
| 40 A | 50 A | 8 AWG | 6 AWG |
| 48 A | 60 A | 6 AWG | 4 AWG |
| 64 A | 80 A | 4 AWG | 3 AWG |
See what size breaker you need for an EV charger for the full 16–80 A table, or let the free wire and breaker size calculator do it for copper or aluminum.
Derating: when the table value isn't enough
Table 310.16 assumes no more than three current-carrying conductors in a raceway or cable and an ambient temperature of 30 °C (86 °F). Adjust before you pick the size if:
- More than three current-carrying conductors share a conduit (Table 310.15(C)(1)).
- The conduit runs through a hot attic or across a sunny rooftop (Table 310.15(B)(1) and 310.15(B)(2)).
THHN's 90 °C rating helps here: you derate from the 90 °C value, then the result can't exceed the 75 °C value.
Long runs
At 240 V and 48 A, 6 AWG copper drops about 1.7% at 85 ft and passes the recommended 3% at about 150 ft. Past that, go to 4 AWG copper, and upsize the ground in proportion (250.122(B)). Our guide to voltage drop on long EV charger runs has the formula and a table, and the voltage drop calculator gives the smallest size that stays under 3%.
Before you buy the wire
- Check the charger manual for terminal size limits and whether it needs a neutral (most don't).
- Confirm the panel can carry the new load with the load calculator.
- For outdoor or underground runs, use wet-rated conductors (THWN-2, XHHW-2).
The EV Charger Calc app sizes the breaker, conductor, ground, voltage drop and conduit fill for the job and puts it all in a PDF quote.
Frequently asked questions
Can I use 6 AWG NM-B for a 48 amp charger?
No. NM-B is limited to the 60 °C column, where 6 AWG copper is rated 55 A. The circuit needs 60 A, so use 4 AWG NM-B (70 A), or 6 AWG THHN in conduit.
Can I use 8 AWG wire for a 48 amp charger?
No. 8 AWG copper is 50 A at 75 °C, below the 60 A the circuit needs. 8 AWG is right for 32 A and 40 A chargers.
What size ground wire for a 60 amp EV charger circuit?
10 AWG copper or 8 AWG aluminum, from Table 250.122. If you upsize the circuit conductors for voltage drop, upsize the ground in proportion.
Does a hardwired EV charger need a neutral?
Most Level 2 chargers don't: two hots and a ground. Check the installation manual; a few models need a neutral.