What Size Wire for a 48 Amp EV Charger?

60 A breaker, 6 AWG copper THHN in conduit or 4 AWG NM-B: why the cable type changes the answer, plus aluminum, the ground, conduit size and long runs.

The EV Charger Calc team

Nov 22, 2026 · 3 min read

Close-up of bundles of stranded copper wire

A 48 A charger is the most common hardwired Level 2 install, and the wire size question has two right answers depending on how you run it. Here's why, and which one to use.

Step 1: 48 A becomes 60 A

NEC 625.41 treats EV charging as a continuous load. The branch circuit and the overcurrent device must be at least 125% of the charger's maximum load:

48 A × 1.25 = 60 A

So: a 60 A two-pole breaker, and conductors with an ampacity of at least 60 A.

Step 2: pick the column

Table 310.16 gives three ampacities for each size: the 60 °C, 75 °C and 90 °C columns. Which one you can use depends on the wiring method and the terminals.

  • 110.14(C): the final ampacity can't exceed the temperature rating of the weakest termination. Breakers and chargers are usually rated 75 °C.
  • 334.80: NM-B cable is limited to the 60 °C column, whatever its conductors are rated.
  • THHN/THWN-2 in conduit is rated 90 °C, but with 75 °C terminals you use the 75 °C column. The 90 °C value is only a starting point for derating.

THHN in conduit: 6 AWG copper

With 75 °C terminations on both ends, 6 AWG copper THHN is good for 65 A in Table 310.16, which covers the 60 A circuit.

Aluminum in conduit needs 4 AWG (65 A at 75 °C), with terminals marked AL/CU.

NM-B cable: 4 AWG copper

NM-B is limited to the 60 °C column. 6 AWG NM-B is only 55 A, not enough for a 60 A continuous load, so step up to 4 AWG NM-B (70 A).

Since 4 AWG NM-B is expensive and stiff, many electricians run 6 AWG THHN in conduit instead, especially in a garage where the run is exposed anyway.

The whole circuit at a glance

PartCopper in conduitNM-B cableAluminum in conduit
Breaker60 A 2-pole60 A 2-pole60 A 2-pole
Conductors6 AWG THHN/THWN-24 AWG copper NM-B4 AWG XHHW-2 or THHN
Ampacity used65 A (75 °C)70 A (60 °C)65 A (75 °C)
Ground (250.122)10 AWG CuIn the cable8 AWG Al or 10 AWG Cu

Two 6 AWG THHN conductors and a 10 AWG ground fit comfortably in 3/4 in EMT; check Chapter 9 fill if you add a neutral or other circuits.

Other charger sizes

ChargerCircuitCu THHN (75 °C)Cu NM-B (60 °C)
32 A40 A8 AWG8 AWG
40 A50 A8 AWG6 AWG
48 A60 A6 AWG4 AWG
64 A80 A4 AWG3 AWG

See what size breaker you need for an EV charger for the full 16–80 A table, or let the free wire and breaker size calculator do it for copper or aluminum.

Derating: when the table value isn't enough

Table 310.16 assumes no more than three current-carrying conductors in a raceway or cable and an ambient temperature of 30 °C (86 °F). Adjust before you pick the size if:

  • More than three current-carrying conductors share a conduit (Table 310.15(C)(1)).
  • The conduit runs through a hot attic or across a sunny rooftop (Table 310.15(B)(1) and 310.15(B)(2)).

THHN's 90 °C rating helps here: you derate from the 90 °C value, then the result can't exceed the 75 °C value.

Long runs

At 240 V and 48 A, 6 AWG copper drops about 1.7% at 85 ft and passes the recommended 3% at about 150 ft. Past that, go to 4 AWG copper, and upsize the ground in proportion (250.122(B)). Our guide to voltage drop on long EV charger runs has the formula and a table, and the voltage drop calculator gives the smallest size that stays under 3%.

Before you buy the wire

  • Check the charger manual for terminal size limits and whether it needs a neutral (most don't).
  • Confirm the panel can carry the new load with the load calculator.
  • For outdoor or underground runs, use wet-rated conductors (THWN-2, XHHW-2).

The EV Charger Calc app sizes the breaker, conductor, ground, voltage drop and conduit fill for the job and puts it all in a PDF quote.

Frequently asked questions

Can I use 6 AWG NM-B for a 48 amp charger?

No. NM-B is limited to the 60 °C column, where 6 AWG copper is rated 55 A. The circuit needs 60 A, so use 4 AWG NM-B (70 A), or 6 AWG THHN in conduit.

Can I use 8 AWG wire for a 48 amp charger?

No. 8 AWG copper is 50 A at 75 °C, below the 60 A the circuit needs. 8 AWG is right for 32 A and 40 A chargers.

What size ground wire for a 60 amp EV charger circuit?

10 AWG copper or 8 AWG aluminum, from Table 250.122. If you upsize the circuit conductors for voltage drop, upsize the ground in proportion.

Does a hardwired EV charger need a neutral?

Most Level 2 chargers don't: two hots and a ground. Check the installation manual; a few models need a neutral.